Intelligent 3151 series transmitter adopts digital technology and special
integrated circuit & surface mounting technology to ensure performance
and reliability. This product has remote communication function as well
as inner range and zero adjustment buttons, convenient to reset range
and zero position. Output can be linear or square roots through software.
Besides, this meter can add a digital communication signal to 4~20mA
to check and diagnose without stop process output, finally remote enquire
and diagnose transmitter in control room. 3151 series transmitter can
measure micro-differential pressure, large differential pressure, low pressure,
high pressure, liquid, vacuum and gravity. It can also measure flow when
matched with throttling device without extractors.
Product features:3151 series differential transmitter is used to measure
liquid level, density and pressure of liquid, gas, steam, then transfers it to
4~20mA DC current signal. Communicate with computer to set and monitor.
3151DP |
Differential pressure transmitter | ||||||
|
code |
range | |||||
3 4 5 6 7 8 |
0-1.25 to 7.64kPa 0-6.22 to 37.39kPa 0-31.08 to 186.46KPa 0-117.21~689.48Kpa 0-0.34~2.07KPa 0-1.17~6.89Kpa | ||||||
|
code |
output | |||||
A |
4~20mA with HART | ||||||
|
code |
Pressure volume chamber |
Release valve |
isolation diaphragm |
Filling oil | ||
22 23 24 25 33 35 44 73 |
316SST 316SST 316SST 316SST Hastelloy C Hastelloy C Monel 316SST |
316SST 316SST 316SST 316SST Hastelloy C Hastelloy C Monel Hastelloy C |
316SST Hastelloy C-276 Monel Tantalum Hastelloy C-276 Tantalum Monel Hastelloy C-276 |
Silicon oil | |||
2A 2B 3B 2D 3D 7B |
316SST 316SST Hastelloy C 316SST Hastelloy C 316SST |
316SST 316SST Hastelloy C 316SST Hastelloy C Hastelloy C |
316SST Hastelloy C-276 Hastelloy C-276 Tantalum Tantalum Hastelloy C-276 |
Fluorion oil | |||
Code |
Optional items | ||||||
S |
1/2NPT Female thread 316LSST | ||||||
0 |
1/4NPT Female thread 316LSST | ||||||
|
code |
0~100% linear scale indicator bend bracket pipe installed(ø51 mm) Bend bracket plate installed flat bracket pipe installed(ø51 mm) Explosion-proof type d II CT6 Intrinsic safe type, ia II CT6 | |||||
M11 B1 B2 B3 Ed Ei | |||||||
3151DP |
4 |
A |
22 |
|
M11B3 |
Complete model of transmitter |