  • Product number:MC-000042005437
  • Product name:smart power meter
  • Product Type:HR-WP-W
  • Product nameplate:SAIC
  • Project Category:display record >> alarm device >>
  • Manufacturer:Shanghai Automation Instrumentation Co., Ltd.
  • Sales unit: Shanghai Automation Instrumentation Marketing Center
  • Information download:Click to enter the download page  
  • Introduction
  • Specifications
HR series of AC thermal measuring controller, use full isolated technology, directly collect voltage and current transformer signal, calculated frequency, voltage and current, and phase difference and single-phase active power P=U.I.CosΦ or three-phase active power P=√3×U×I×COS(φ+30), Formula of reactive power: reactive power= Apparent power- active power
specific integrated chip, with reliable anti-jamming and stable function
can modify display range, transmission range, alarm value and alarm mode online
soft, hard ware combined anti-jamming type, reduce field jamming signal efficiently
Digital calibration technology
Isolated light and electric technology
With RS232 or RS485 communication function, use standard MODBUS RTU protocol
Brand
Model
HR-WP-W/W0
XC/XS40、80、XC90 series
Characteristics
Display mode    four LED display measuring value each row(PV)
Display range   0~9999。
Measuring accuracy:  0.5%FS±1 byte
Resolution    ±1 byte
Alarm mode   1-2-way control (lower limit L、upper limit H)LED indication
Alarm accuracy   ±1 byte
Setting mode   touch button and digital setting, Setting value can be permanent saving
Input signal
AC 0~500V direct input,converted to 100V voltage by voltage transformer, if more than 500V
AC 0~5A direct input,converted to 5A voltage by current transformer, if more than 5A
 
Output signal
Output accuracy 0.5%FS±1 byte
Current signal   DC 4~20mA,load resistance R≤500Ω;DC 0~10mA,load resistance R≤750Ω。
Voltage signal   DC 0~5V;DC 1~5V,load resistance  R≥250KΩ,or not ensure output accuracy
Alarm output   relay control output─ relay ON/OFF with hysteresis
Communication output:   baud rate─1200~9600bps free setting, use standard MODBUS RTU communication protocol
Using environment
Environment temperature:   -10~55℃;
Environment humidity   10~90%RH。
Compressive strength:   input/output/power/communication ≥1000V.AC 1minute
Isolated resistance:    input/output/power/communication ≥100MΩ。
AC power   90~265V(switch power),frequency:50Hz/60Hz;
AC power   24V±2V(switch power)
Power consumption  <5W。