range:0-3m/s~0-40m/s
output signal:4-20mA(2-wire);0-10V(3-wire) 0-5V(3 -wire)
Medium: Air and non-flammable gas, compatible gases
Stability:±1%F.S/year
temperature range:-10℃ to 50℃
power supply:10-35VDC(2-wire);17-36VDC or isolated 15-26VAC(3-wire)
power consumption:Max. 40mA
response time:Field continuously adjustable 0.5-15 seconds
Pitot tube K coefficient adjustment range:0.5-3.0
Zero and range adjustment:Key way + jumper
Loop impedance:current output 0-1250 Ω;
Minimum load voltage output :1000 Ω。
display:4 digits LCD display。
Electrical connection:4-20mA output,2 Line Continental Terminals;
0-