Explosion-proof mark ExdIIBT4
Qualified number GYB05113
Use area 1area、2 area、IIA、IIB,T1~T4 dangerous area
Configuration features Through the PC, using the TMT181A configuration tool to configure
Input Signal Type Thermal resistance, all kinds of thermocouples, resistance, millivolt signal
range set through PC and special interface
Conversion Accuracy ≤0.1%
Output signal analog 4~20mA 20~4mA
Cold Junction Accuracy ±1℃(thermocouple)
Max load (V power -14.8V)/0.025A(current input)
Limit current ≤25mA
Response time 1s
Display digit four digits
Isolated voltage 1500kVAC (input/output)
Power voltage 14.8~35VDC
Long-term stability <0.01% FS/1℃
Protection level IP66
Ambient temperature -20℃~+40℃