  • Introduction
  • Specifications
AD181F Field mounted Temperature Transmitter is a smart PC configurable temperature transmitter. It can receive 2, 3, 4-wire RTD, thermocouples, resistance or millivolt input and linearly deal with the input signal then output 4~20mA standard signal. It has the feature of electrical isolation and pre-set for sensor damaged and short-circuit fault signal.
AD181F field mounted temperature transmitter installed on the domestic-style aluminum case. It is water-proof and dust-proof.
Configuration features           Through the PC; use AD181 configuration tool can be configured
Input signal type      thermal resistor, thermocouple, resistance and millivoltage signal           
range                set by PC interface
Conversion Accuracy                ≤0.1%
Output signal                Analog  4~20mA
Cold Junction Accuracy               ±1℃(thermocouple)
Max load                (V-11.5V)/0.025A(power output)
Limit current                   ≤25mA
Response time                 1s
Isolated voltage                1500VAC(input/output)
Power voltage                11.5~35VDC
Temperature drift                0.01% FS/1℃
Protection level               IP66(AD181FDA) IP64(AD181FDP)
Ambient temperature               -25~+75℃