- Home
- |
- About us
- |
- Certificate
- |
- Products
- |
- Performance
- |
- Member
- |
- News
- |
- Technical Support
- |
- Contact us
Brand |
Model No. |
HR-WP-Cos |
XC/XS40、80、XC90 series |
features |
Display mode: measuring value(PV)displayed by LED
Display range: 0~9999。
Measuring accuracy: 0.5%FS±1 bytes;±0.2%FS±1 bytes
Resolution: ±1byte
Alarm : 1-2 way alarm control(lower limit L、upper limit H)LED indicating。
Alarm accuracy : ±1byte
|
Input signal |
AC 0~500Vdirect input
AC 0~5Adirect input |
Output signal |
Output accuracy: 0.5%FS±1 bytes;±0.2%FS±1 bytes
Current signal: DC 4~20mA,load resistance R≤500Ω;DC 0~10mA,load resistance R≤750Ω。
Voltage : DC 0~5V;DC 1~5V,load resistance R≥250KΩ,otherwise can not keep the output accuracy after connected with outside instrument
Alarm output: relay control-relay ON/OFF
Communication output: baud─1200~9600bps setting inside,with standard MODBUS RTU communication protocol |
Environment conditions |
Environment temperature: -10~55℃;
Temperature humidity: 10~90%RH。
Pressure strength: input/output/power/communication ≥1000V.AC 1 minute
Isolation resistance: input/output/power/communication ≥100MΩ
AC power: 90~265V(switch power), power: 50Hz/60Hz;
DC power: 24V±2V(switch power)
Power consumption<5W |