Explosion-proof mark:[Exia]ⅡC
power:24V DC±10%
power consumption: 2.8W
Danger zone signal output equivalent circuit
Maximum output voltage:24V
Minimum Output Voltage:12V
Safety zone signal input:
Input switch is connected、Transistor turn-on or terminal 1、2 logic electric level ≤1V、supply power to the danger zone。
Input switch is open,Transistor turn-off or terminal 1、2 logic electric level≥4V,do not supply power to the danger zone。
CQST certification parameter(9,10 terminal)
U0:25V、I0:185mA,P0:1156mW、UM:250V
ⅡA:C0:2.79μF、L0:30mH
ⅡB:C0:0.48μF、L0:15mH
ⅡC:C0:0.11μF、L0:3,5mH,