Explosion-proof mark: Ex(ia)ⅡC
transfer accuracy: ±0.2%×F•S
allowable input signal in dangerous area:
three-wire hot resistance:Pt100、Cu100、Cu50、BA2、BA1、G
linear resistance:0-400Ω
input signal to safety area:
DC current:0~10mA、4~20mA、0~20mA
DC voltage:0~5V,1~5V,0~10V
NEPSI certification parameter(between 9 and 11 terminal;10 and 11terminal):
Uo=8.7V,Io=27mA,Co=3.0μF,Lo=20mH
apply range:
hot resistance:Pt100、Cu100、Cu50、BA2、BA1、G
linear resistance:0-400Ω
communication(in safety area):RS232 or RS485 interface
power supply:DC 24V±10%
power consumption:1.2W(single-loop 20mA output);1.8W(dual-loop 20mA output)
case size:22.5×100×115mm