Explosion-proof mark:Ex(ia)ⅡC
allowable input signal in dangerous area:
active signal:input signal>2.1mA,
input signal <1.2mA,means OFF
input signal to safety area:
allowable load:AC220V 1A,DC24V 3A
Electrode Open Output:
external power supply:<40V DC,switch frequency≤5kHz。
current input ≤40mA, Short-circuit current <100mA。
NEPSI certification parameter(between 9 and 10 terminal):
Uo=10.5V,Io=16.2mA,Co=1.7μF, Lo=94.8mH
apply scope:Proximity switch、active and passive switch
communication:RS232 or RS485 interface
power supply:DC 24V±10%
power consumption:1.1 W
case size:22.5×100×115 mm