Configuration features Through the PC, using the TMT181A tool can be configured on line or through the SETUP connector can be configured on line in measurement process
Input signal type Thermal resistance, all kinds of thermocouples, resistance, millivolt signal
Range set through PC and special interface
Conversion Accuracy ≤0.08%
Output signal analog 4~20mA 20~4mA
Cold Junction Accuracy ±1℃(thermocouple)
Max load (V power-8V)/0.025A(current output)
Limit current ≤25mA
Response time 1s
Isolation Voltage 2kVAC(input/output)
Power voltage 8~35VDC
Long-term stability ≤0.1℃/year,or 0.05%/year
Ambient temperature -40~+85℃